Pressure Test Safety Distance Verification Tool

Hydro Test / Pneumatic Test — Calculation Verification Aid

Important Limitation: This tool provides a calculation-based recommended minimum safety distance and supports verification against the entered distance verification criteria. The final field application shall consider project/client requirements, projectile assessment, PTW, JHA, SIMOPS assessment and approval by the Responsible Supervisor or other competent person.

Hydro Test Input Values

bar(g)
mm
m
kg/m³
Distance Verification Criteria
Optional criteria used for verification status. The highest entered value among these criteria is compared with the calculation-based recommended minimum safety distance.
m
m

Hydro Formula / Basis

alpha = Li / (Di / 1000)

L = 0.15 × (Di / 1000) × alpha0.4 × [ Pt / (Rho / 1000)0.33 ]0.6

Hydrostatic calculation is retained as a legacy Lloyd’s Register 96-02 / T-0240 based verification aid. It shall not replace engineering review. Trapped air, end-cap/blind failure, line-of-fire, hose whip, supports, anchors, SIMOPS and public interface must be assessed separately.
Alpha Factor
-
Formula Distance - L
-
Calculation-Based Recommended Minimum Safety Distance
-
Verification Status
-

Report Information

Final Field Application Rule: The exclusion zone applied on site shall consider the calculation-based recommended minimum safety distance, project/client minimum requirement, JHA result, SIMOPS restriction, fragment/projectile assessment, and Responsible Supervisor / competent person approval.